X-PoE companion

Voltage drop, dimming, and what people can actually see.

Model lighting runs with 36V and 48V fixtures, 23AWG or 22AWG conductors, and the 1115mA per-channel X-PoE output limit. The chart shows why full-output drop numbers can overstate what happens when scenes are dimmed.

Port context

X-PoE has 2 channels per port. This estimator calculates per channel so fixture current and run length stay easy to reason about.

Inputs

Defaults represent a typical 36V lighting load on 23AWG cable.

Available before cable: 52.5V?This is switch input voltage minus the internal switch drop. Cable drop is subtracted after this, then the result is compared with fixture forward voltage.

Load current model?The calculator derives fixture current from load power: watts divided by fixture forward voltage. The channel current limit is only a cap; it is not a second load input.

Current used: 1,111 mA = min(40.0W / 36.0V, 1,115mA cap)

Wire gauge?Wire gauge sets conductor resistance. 23AWG is the default; 22AWG has lower resistance and therefore less cable drop.

Run lengths?Enter one-way cable length from the X-PoE output to the fixture. The model uses round-trip conductor length for voltage drop.

Fixture summary

Absolute max one-way run

300 ft+

Load current used

1,111 mA

Voltage leaving switch

52.5 V

Power at current limit

40.1 W

Fixture load power

40.0 W

Entered rated output

3,000 lm

Current limit active

No

At full output, this fixture has enough voltage headroom to stay above forward voltage through the 300 ft planning range. The channel has 16.5V of headroom before cable loss, using a 36.0V forward-voltage threshold and 52.5V available before the cable.

Run

70 ft

23 AWG
Voltage drop
3.17 V
Fixture terminal voltage
49.33 V
Forward-voltage headroom
13.33 V
Drop of fixture voltage
8.80%
Cable loss
3.52 W
Estimated delivered lumens
3,000 lm
Perceived lightness
100.0 L*

Run

100 ft

23 AWG
Voltage drop
4.52 V
Fixture terminal voltage
47.98 V
Forward-voltage headroom
11.98 V
Drop of fixture voltage
12.57%
Cable loss
5.03 W
Estimated delivered lumens
3,000 lm
Perceived lightness
100.0 L*

Run

300 ft

23 AWG
Voltage drop
13.57 V
Fixture terminal voltage
38.93 V
Forward-voltage headroom
2.93 V
Drop of fixture voltage
37.70%
Cable loss
15.08 W
Estimated delivered lumens
3,000 lm
Perceived lightness
100.0 L*

Comparison at 100% dimming

70 ft to 300 ft extra cable drop

10.41 V

Estimated lumen difference

0 lm

Perceived difference

0.0 L*

Forward voltage is a threshold

The fixture does not use every extra volt as more light. It needs enough terminal voltage to stay above forward voltage at the commanded current.

Current drives drop

Voltage drop is I x R. When a scene dims, current falls with the command, so the wire drop falls with it.

Distance matters visually

A 70 ft and 100 ft run are usually not adjacent at the same task plane. Spatial separation reduces direct comparison.

Individual dimming behavior

Each run on its own

These charts remove the side-by-side comparison and show what each cable length does over the dimming range, including perceived lightness.

Estimator notes

This model assumes copper conductors, one-way run length entered by the user, round-trip conductor resistance, and a dropout threshold: switch input voltage minus internal switch drop minus cable drop must remain above fixture forward voltage. Above that threshold, estimated lumens follow the dimming command. Below it, the model marks the fixture as off/dropout. Real fixtures and LED drivers can regulate, fold back, flicker, or fail differently, so use this to explain order-of-magnitude behavior and compare scenarios, not as a compliance certification.